Download this case study or listen to the webinar recording here.
When the Canterbury dialysis unit updated its water purification system with the installation of a new reverse osmosis plant in 1997, it was soon apparent that large volumes of reject water were being ‘lost to drain’. Within two years, and with the help of the hospital’s Estates Department, a simple system capable of recycling 800 litres of this water per hour was installed at a cost of £15,000. The system has now been running for over ten years, saving the Trust £7,500 each year on mains water and sewerage costs.
The salvaged reject water is directed to a recovery tank in the basement. From there it is pumped up to the grey water tank on the roof, which then supplies the water to the hospital toilets. Float switches divert reject water to the drain if the grey water tank becomes full, and diverter valves direct the reject water directly to the drain from the reverse osmosis system during monthly chemical disinfections.
The Thomas Becket Dialysis Unit, Kent & Canterbury Hospital.
A similar system was included in a new-build satellite dialysis unit in Ashford, where the conserved water feeds into the local laundry room. Because water recovery was designed in from the start, the costs were much lower: just £2500.
The reverse osmosis system in the Ashford Satellite Dialysis Unit.
“Back in 1999 I was amazed how simple this all was to do – 10 years later, given the savings we’ve made, I’m amazed nobody else has done it too.”
Steve Milne, Renal Technical Manager, Kent and Canterbury Hospital, UK.
Haemodialysis has a considerable environmental impact, commonly requiring frequent patient travel, using large amounts of electricity and producing significant plastic and packaging waste. Furthermore, it consumes vast quantities of water. Producing the 120 litres of dialysate required for a typical four hour session requires approximately 400 litres of mains water. Reverse osmosis is an important step in the purification process that this water undergoes (see figure 1). Reverse osmosis systems vary in efficiency, but commonly reject up to two thirds of the water presented to them. Termed ‘reject water’, this high grade grey water does not come into contact with the patient at any stage and poses no infection risk, yet it is needlessly ‘lost to drain’ in almost all dialysis facilities. This guide outlines a simple methodology for salvaging reject water so that it can be put to an alternative use, such as in the hospital laundry or sanitation systems, to produce steam for equipment sterilisation or to feed low-pressure boilers.
Figure 1.
There are a number of reasons why a dialysis unit might wish to salvage the reject water it produces. The financial benefits are, of course, important. The NHS is experiencing budget cuts related to the current financial crisis. Recycling reject water offers considerable savings on mains water costs (which are predicted to rise), and also avoids the need to pay to put the reject water into the sewer. Secondly, compliance with carbon targets is of increasing importance, as impending regulatory and fiscal policies for carbon reduction will impact fundamentally on the cost and quality of healthcare provision. The NHS Carbon Reduction Strategy establishes NHS targets for reducing carbon emissions, and the Carbon Reduction Commitment will apply to individual Trusts from April 2010. Conserving reject water will help trusts to meet these targets. Thirdly, there are strong environmental reasons for saving water. Water is a finite natural resource. Climate change and population growth are leading to increasing water scarcity and many people now live in water-stressed areas. We all therefore have a responsibility to use water conservatively. Finally, this project allows Local Trusts to demonstrate good corporate citizenship, highlighting their decision to put social, economic and environmental considerations at the heart of their decision making.
The physical constraints imposed by the existing layout of the renal unit and the available space may pose a barrier to a financially-viable water conservation system. An example that this case study demonstrates is the possible need for an extra water tank (as water cannot be pumped directly out of a reverse osmosis system, but must be allowed to drain at the rate it is produced). An extra tank will not always be necessary, but will of course require storage space. Similarly, the conserved water must be directed to its intended site of use, and consideration must be given to the practicality and cost of installing the necessary pipework. For reasons such as these, it is essential to gain the support of the local Estates department.
The financial costs will vary from unit to unit, and may dictate whether a water conservation project is viable. However, in most cases, the costs will be small and the potential savings great. For example, the cost of incorporating the methodology into the design of the Ashford satellite unit was only £2500 (tank and control panel £1300; piping £1200). The piping was laid alongside other services required by the new build, so no cost was incurred for groundwork. The running costs of any pumps required must also be considered although, again, these are likely to be small. The cost of running the pump at the Ashford unit is less than £100 per year.
The cost of implementing the methodology at the Canterbury unit has been estimated at £15,000 in 1999. It is also possible to replace existing reverse osmosis systems with newer and more efficient ones which reject less water; this will of course increase the implementation costs (when compared to leaving existing systems in-situ), but is outside the scope of this case study.
The return on investment will depend upon:
In general, the return on investment is likely to be greater for a new-build unit, where the installation costs may be lower, and there is greater flexibility in arranging an appropriate alternative use for the salvaged water. This is borne out in our case studies:
| Canterbury (retrofit) | Ashford (built in) | |||||
|---|---|---|---|---|---|---|
| Year | Investment | Savings to date | ROI | Investment | Savings to date | ROI |
| 1 | £15,000 | £7,500 | 50% | £2,500 | £10,558 | 422% |
| 2 | 0 | £15,000 | 100% | 0 | £21,116 | 844% |
| 5 | 0 | £37,500 | 250% | 0 | £52,790* | 2112% |
| 10 | 0 | £75,000 | 500% | 0 | £105,580* | 4223% |
* Projected figures
The finite volume of water on the earth is constantly being recycled and purified; it evaporates off the earth, condenses to form clouds, before precipitating down as rain. Back on earth, the water runs off into rivers, lakes, reservoirs and seas, or percolates down into the earth’s natural underground reservoirs. But the fresh water in this cycle is being used by humans at a rate faster than the recycling process can replenish, and more than one third o f the world’s population now live in water-stressed countries. So we must use water wisely. A ‘carbon footprint’ does not therefore do full justice to the environmental benefits of water conservation. However, energy is also required to treat and move the water that we use, and conserving water therefore also saves energy and reduces the carbon footprint of the renal unit.
Accounting for the energy used to power the pump, the carbon savings at the Ashford unit are approximately 750 kg CO2 equivalents per year. This figure is reached by a two step calculation. Firstly, calculate the carbon savings made by recycling the reject water in place of mains water. To do this, apply a mains water life-cycle conversion factor (available from, for example, the DEFRA website) to the volume of water saved per year. Secondly, subtract from this the carbon cost of any electricity required to pump the water to its place of use over the course of a year (this second step requires you to know the power of the pump, the duration of its use during the year, and a conversion factor for electricity to carbon consumption).
Carbon savings (kg CO2e/year) = [Volume water saved in one year (L) x mains water carbon conversion factor (kgCO2e/L)] – [electricity used for pumping per year (kWh) x carbon conversion factor (kgCO2e/KWh)]
Careful planning and calculations should negate the main risk – that physical barriers, or miscalculations regarding the amount of reject water produced, render the project financially unviable.
It is also important to ensure that the new use supplied by the recycled reject water (e.g. laundry or hospital toilets) has a back-up mains supply to cover any interruptions (for example during maintenance or disinfection).
The case studies and discussion outlined above includes most of the information required to develop a sound business case for a water conservation project in a dialysis unit. The following guidance will help you explore the practicalities and assess the financial benefits further.
Listen to webinar recording on water savings in haemodialysis (via the 2degrees network) here.